EDAC 400-24
24 Volt 4 configurable inputs & outputs (inputs digital only), 16 numbers, voice, numeric & alpha-numeric paging.
Features
- Cost-effective auto-reporting dialler
- Compact design, easy installation
- Activated by contact closure or opening
- Transmits 8-second voice message or 20-character pager/SMS
- Alarm notification call to a list of phone numbers or pagers
- Interrogated via telephone keypad
- User-programmable phone numbers, messages, and functions
- Flexible telemetry monitoring tool
Specifications
- Inputs: 4 clean-contact, voltage-free triggers
- Outputs: Up to 4 open collector type (maximum current 120mA per output)
- Power: 10-30V DC, 40mA idle, 80-100mA active
- Telecom Line: 2 RJ11 sockets
- RS232 Connector: Used for programming or providing 2400 baud modem connection to external device
- Mechanical: 192mm x 110mm x 35mm, 250g, aluminum cabinet, white epoxy powder coat finish
- Messages: 4 seconds of high-quality user-recordable speech per input or status
- Parameters: 4 phone numbers per input, up to 20 digits per number, variable call playtime and wait time
- Dialling mode: DTMF (tone dialling)
- Numeric Paging: 20-digit numeric string transmission to pagers
For more detailed information, download the full manual.
PB20
The PB20 is designed to be used with EDAC products. The unit produces a continuous output of 13.8V DC at loads up to 4A. During mains fail the internal battery can maintain operation for periods from one hour upwards depending on load. The 13.8V output is electrically regulated, providing a constant voltage over the 0 to 4A output current range and providing standby charging of the battery.